The Mercoid MPC Pump Controller provides versatile level control
in a standard 1/4 DIN package. Designed for use with almost any style
level transmitter the unit displays the present level and main set point
value. Incorporated in the MPC is programmable level differential for
on/off control of one or two pumps, valves, or other devices through two
SPDT relays. Also featured are two additional programmable alarm contacts
with front alarm light indication.
The MPC is flexible and incorporates a user-friendly programming menu.
The front face meets NEMA 4X for outdoor panel mounting. So many features
are combined into the MPC that it eliminates many components in a pump
control system.
NEW FEATURES
- Alarm can be programmed for output indication of pump seal failure
or over temperature.
- Selectable time delay, for pump two, on power up to prevent both
pumps from starting at the same time. If power is lost, upon regaining
power a time delay of up to 60 seconds can be selected to prevent too
large of a current draw.
FEATURES
- Selectable pump alternation when used with two pumps to minimize pump
wear. With alternation on a seal failure or over temperature condition
will force the non-failed pump to lead status and stop alternation.
- When used with a submersible pump including a moisture sensor the
MPC has alarm light indication of seal failure.
- When used with a pump including a thermostat the MPC has alarm light
indication of pump over temperature and removes the pump from service.
The Pump can be brought back into service automatically or by manual
reset when the pump has cooled down.
- Integral 24 VDC power supply for level transmitter.
- Displays pump run time from a front panel button.
- Test System function that simulates the process input to insure the
pumps are operating or to test programming.
- User selectable security lock-out of programming and/or set points.
- Process input retransmission as a current (4 to 20 mA) or voltage (2
to 10 VDC) analog signal*.
* Standard model MPC is set for current retransmission. For voltage retransmission
add suffix -RV
|
SPECIFICATIONS Inputs: 4
(or 0) to 20 mA DC or 2 (or 0) to 10 VDC selectable. Input
Impedance: Current = 10 ohms, Voltage = 100 K ohms. Output
Ratings: Control Relays: SPDT, rated 10A @ 240
VAC res., 1/4 hp @ 120 VAC, 1/3 hp @ 240 VAC. Alarm
Relays: SPST, 3A @ 240 VAC res., 1/10 hp @ 120 VAC. Control
Type: On/off, reverse (pump out) or direct (pump in) acting. Power
Requirements: 100 to 240 VAC nominal, +10%-15%, 50 to 400 Hz, single
phase; 132 to 240 VDC nominal, +10%-15%. Power Consumption: 7.5
VA maximum. Accuracy: ±0.25% of span, ±1 least significant
digit. Display: Two 4 digit, 7 segment 0.56" high
LED’s. Display Resolution: 1 count. Memory Backup:
Nonvolatile memory (no batteries required). Serial
Communications: Optional RS-232 or RS-485 with Modbus®
protocol. Ambient Operating Temperature/RH: 14 to 131°F (-10
55°C)/0 to 90% up to 104°F (40°C) non-condensing, 10 to 50% at 131°F
(55°C) non-condensing. Weight: 16 oz. (454 g). Front Panel
Rating: Meets UL Type 4X (IP66). Loop Power Supply
(isolated): 24 VDC @ 50 mA, regulated. Seal Failure (Moisture
Sensor): Power: 2.5
VDC. Search Current: 3 micro
amps. Resolution: 10K to 500K ohms in 10K ohm
steps. Agency Approvals: UL 508.
ACCESSORIES: Weatherproof
Enclosures, NEMA 4X.
For compatible level transmitters see
Mercoid Series SBLT and PBLT.
A-901
OPTIONS: RS-232 Modbus®-RTU Serial
Communications. Allows remote computer to read and write all control
parameters. Add suffix - 232 RS-485 Modbus®-RTU Serial
Communications. Allows remote computer to read and write all control
parameters. Add suffix - 485
|